NORMAL START-UP PROCEDURE
AFTER THE INITIAL
START-UP PROCEDURE HAS BEEN FOLLOWED CONFIRMING THE PROPER OPERATION OF THE
GUARDIAN, AND RELATED EQUIPMENT, THE UNIT CAN BE PUT INTO NORMAL OPERATION.
THE HEATER CAN BE RE-STARTED USING THE FOLLOWING PROCEDURE UPON UNIT SHUTDOWN.
1) FIRST CORRECT THE CAUSE OF THE SHUTDOWN PRIOR TO PROCEEDING, I.E. LOW PILOT
GAS PRESSURE, PLUGGED ORIFICE, UNSTABLE PILOT FLAME, ETC.
2) RESET THE
GUARDIAN PANEL . WATCH FOR PROPER BATTERY VOLTAGE AND SPARK
INDICATION.
3) VISUALLY CONFIRM THAT THE PILOT FLAME HAS BEEN
ESTABLISHED.
4) MANUALLY OPEN THE MAIN BURNER FLAME IGNITION.
5)
VISUALLY INSPECT THE CONDITION OF THE MAIN FLAME FOR COLOR, SHAPE, LOCATION,
ETC. |