SYMPTOM |
PROBLEM |
SOLUTION
|
| ELECTRODE
FAILS TO SPARK |
HEAVY SOOT
ACCUMULATION ON ELECTRODE OR PILOT TIP |
REMOVE & CLEAN PILOT TIP
AND ELECTRODE |
| IGNITION CABLE
DAMAGED |
BROKEN OR
BURNED |
REPLACE WIRE |
| LOW BATTERY
VOLTAGE |
|
CHARGE OR REPLACE AS
REQUIRED |
| POOR
CONNECTIONS TO ELECTRODE OR BATTERY |
|
CLEAN & TIGHTEN ALL
CONNECTIONS TO BATTERY & ON TERMINAL BLOCK |
| PILOT FLAME
FAILS |
IMPROPER
PLACEMENT OF ELECTRODE |
PLACE ELECTRODE CLOSER TO
PILOT TIP TO MAXIMIZE ARC |
| NO SPARK ON
ELECTRODE |
|
SEE "IGNITOR FAILS TO
SPARK" |
| NO PILOT GAS
SUPPLY |
|
CHECK FOR CLOSED VALVES OR
PLUGGED ORIFICE, REGULATORS, OR STRAINER |
| BURNED PILOT
TIP |
|
REPLACE PILOT TIP |
| DOES NOT SENSE
THE PILOT FLAME |
ELECTRODE
IMPROPERLY PLACED |
ADJUST ELECTRODE TO ASSURE
GOOD FLAME CONTACT |
| |
IMPROPER PILOT
GAS PRESSURE |
ADJUST PILOT FLAME TO
ASSURE FLAME CONTACT WITH BOTH ELECTRODE AND PILOT TIP |
| |
IMPROPER
GROUND |
INSTALL GROUND WIRE FROM
PANEL TO BURNER PIPEING |
| |
GROUND FAULT
BETWEEN BATTERY NEGATIVE AND VESSEL PIPING |
CHECK ALL WIRING AND VALVES
FOR A SHORT TO PILOT BURNER TIP |
| DAMAGED
IGNITION CABLE |
|
REPLACE CABLE |
| GUARDIAN PANEL
NOT ELECTRICALLY GROUNDED |
|
INSTALL GROUND WIRE FROM
PANEL TO BURNER PIPEING |